TM66E MODULAR

TM66E Modular Three-Phase UPS 40–600 kVA

TM66E Modular 40–600 kVA is a transformerless modular three-phase online double-conversion UPS platform for medium-to-large data centers, telecom, infrastructure and industrial critical-power projects. It uses 40 / 50 / 60 kVA hot-swappable power modules, output PF 1.0, 3-Level IGBT topology, external VRLA or lithium battery systems, 360–600 Vdc battery bus, charger current up to 20 A, ECO / HECO modes up to 99%, Power Walk-In, Load Bus Synchronization (LBS) and N+X parallel operation up to 6 units by configuration.

VRLA / Lithium Support PF 1.0 Output Up to 96% Efficiency Parallel up to 6 Units Hot-Swappable Power Modules

Mid-Range Modular UPS with VRLA & Lithium Support

TM66E Modular 40–600 kVA is a transformerless online double-conversion modular three-phase UPS platform for medium-to-large data centers, telecom, infrastructure and industrial critical-power projects requiring scalable capacity, VRLA or lithium battery flexibility and high-efficiency operation. 40 / 50 / 60 kVA hot-swappable power modules support capacity expansion and reduced-downtime maintenance by approved procedure.

VRLA & Lithium Battery Support

Compatible with external VRLA lead-acid or lithium battery systems by project configuration. The 360–600 Vdc battery bus supports both chemistries with project-specific cabinet design, BMS communication and runtime targets. Charger current is up to 20 A by model and configuration.

40 / 50 / 60 kVA Hot-Swappable Power Modules

Power, bypass, monitoring and ECU control modules are hot-swappable. Power modules in 40 / 50 / 60 kVA ratings can be added, removed or replaced within cabinet capacity, supporting capacity expansion and reduced-downtime maintenance by approved procedure. Cabinet capacity scales from 40 to 600 kVA by module and cabinet configuration.

PF 1.0 Output / Up to 96% Efficiency

Output PF 1.0 (kW = kVA) delivers full usable kW across the 40–600 kVA range. AC-mode efficiency reaches up to 96% with 3-level IGBT topology, while ECO and HECO modes are available up to 99% for energy saving in suitable utility conditions.

Parallel up to 6 Units & LBS

Direct parallel operation supports capacity expansion or N+X redundancy up to 6 units, subject to project design. Shared-battery parallel configuration is supported. Load Bus Synchronization (LBS) supports dual-bus or coordinated multi-system critical-power architectures.

7″ Touchscreen HMI & SNMP / Modbus

7-inch TFT touchscreen is standard, with 10-inch optional by configuration. The system supports mimic diagram, history logs and fault logs. Communications include RS-232, RS-485, parallel, LBS, BMS and dry contact. Optional TM550 SNMP card supports network monitoring, and Modbus RTU via RS-485 supports BMS / SCADA integration. FW / SW online upgrade is supported in bypass mode.

Wide Input & Generator Compatibility

Wide 138–485 Vac input range supports unstable utility conditions, with operation derated to 40% load below 305 Vac. Input PF ≥0.99 and input THDi ≤3% help reduce upstream electrical stress. Power Walk-In limits start-current impact for generator-backed sites when the generator is properly sized and configured.

Expand Your TM66E Modular 40–600 kVA System

Optional system configurations for TM66E Modular 40–600 kVA include 40 / 50 / 60 kVA hot-swappable power modules, VRLA or lithium battery systems, N+X parallel operation with LBS, TM550 SNMP monitoring, BMS integration and ECO / HECO high-efficiency modes – specified according to UPS capacity, battery chemistry, redundancy plan and project design.

40 / 50 / 60 kVA Hot-Swappable Power Modules

40 / 50 / 60 kVA power modules support scalable system capacity from 40 to 600 kVA by cabinet and module configuration. Power, bypass, monitoring and ECU control modules are hot-swappable, supporting capacity expansion and reduced-downtime maintenance by approved procedure.

VRLA / Lithium Battery System

Supports external VRLA lead-acid or lithium battery systems with 360–600 Vdc battery bus by project configuration. Lithium systems require compatible cabinet design, BMS communication and project-specific charging / runtime settings confirmed during sizing.

Charger up to 20 A

Charger current is available up to 20 A by model and configuration, supporting external battery systems sized for the project runtime target. Battery cabinet quantity, battery chemistry, runtime, charging current and BMS integration are selected by ATENCO engineers according to UPS capacity and load profile.

Parallel Kit / LBS Synchronization

Parallel kits support capacity expansion and N+X redundancy up to 6 units by configuration. Load Bus Synchronization (LBS) supports dual-bus or coordinated multi-system critical-power designs, including STS-supported architectures.

ATENCO TM550 SNMP network management card for TM66E Modular 40-600 kVA intelligent slot with BMS integration and HECO monitoring

TM550 SNMP / BMS / HECO Monitoring

Optional TM550 SNMP card enables network monitoring, web access, event alerts, shutdown management and NMS / BMS integration. RS-485 / Modbus RTU supports BMS / SCADA integration by configuration, while ECO / HECO modes support high-efficiency operation in suitable utility conditions.

Technical Details

Complete specifications for the TM66E Modular 40–600 kVA mid-range modular three-phase UPS platform with VRLA and lithium battery support.

Specification80120200300320400500600 kVA
Full NameTM66E Modular Three-Phase UPS 40–600 kVA
TopologyOnline Double-Conversion (VFI), 3-level transformerless, hot-swappable modules
Phase3P–3P (3Ph+N+PE in / 3Ph+N+PE out)
Form FactorModular cabinet; dimensions vary by cabinet configuration (see Physical tab)
Typical Module Configuration2 × 403 × 405 × 40 / 4 × 506 × 50 / 5 × 608 × 408 × 5010 × 5012 × 50 / 10 × 60 kVA
Power Module Sizes40 / 50 / 60 kVA hot-swappable power modules
Output Power Factor1.0 (kW = kVA)
Display7″ TFT touchscreen standard / 10″ optional with mimic diagram, history and fault logs
Battery SupportExternal VRLA lead-acid or lithium battery system; 360–600 Vdc battery bus; sized by project configuration
Operating ModesOnline, ECO, HECO, Bypass, Battery, Maintenance
ParallelUp to 6 units for N+X redundancy or capacity expansion; shared-battery parallel supported
Load Bus Synchronization (LBS)Supported for dual-bus / synchronized multi-system designs by configuration
Generator CompatibleYes – Power Walk-In limits start-current impact on generator capacity
StandardsIEC/EN 62040-1, IEC/EN 62477-1 safety; IEC/EN 62040-2 + IEC 61000 series EMC; IEC 62040-3:2021 performance; CE by series

System capacity from 40–600 kVA by module / cabinet configuration; the standard cabinet matrix shown above reflects factory model combinations. ATENCO engineers can specify smaller-cabinet configurations (down to 40 kVA) by project on request.

Specification80120200300320400500600 kVA
Nominal Input Voltage380 / 400 / 415 Vac (3Ph+N+PE)
Input Voltage Range138–485 Vac (138–305 Vac for 40% load; 305–485 Vac for 100% load)
Input PF≥0.99 at 100% linear load
Input THDi≤3% at 100% linear load
Bypass Voltage Range (Max)+25% (Optional +10% / +15% / +20%); 230 V: +20%; 240 V: +15%
Bypass Voltage Range (Min)−45% (Optional −10% / −15% / −20% / −30%)
Bypass Frequency Range50 / 60 Hz ±10%
Output Voltage380 / 400 / 415 Vac (3Ph+N+PE), ±1% regulation
Output PF1.0 (kW = kVA)
Output THDv (linear)≤2%
Output THDv (non-linear)≤4%
Output Frequency (Line mode)Synchronized with input within selected tracking range; ±1% / ±2% / ±4% / ±5% / ±10% optional
Output Frequency (Battery)50 / 60 ±0.1%
Crest Factor3:1
Transfer Time0 ms AC-to-battery; automatic bypass protection by operating condition
Efficiency (AC Mode)Up to 96% by configuration
Efficiency (ECO Mode)Up to 99%
Efficiency (HECO Mode)Up to 99% by configuration
SpecificationValue
Battery TypeExternal VRLA lead-acid or lithium / LiFePO4 battery system by project configuration
Battery Voltage / DC Bus360–600 Vdc by project configuration
Charging Current (Max)20 A
Charger Type3-stage smart charger
Battery SystemExternal battery cabinets; VRLA strings or lithium / LiFePO4 cabinets by project configuration
Battery Temp SensorOptional via BAT_T port
BMS CommunicationRequired for lithium battery cabinets; optional for VRLA installations by project configuration
DC Cold StartSupported when battery system is installed and available
Lithium Battery SupportSupported by project configuration; requires compatible cabinet design, BMS communication and project-specific charging / runtime settings

Exact battery configuration (VRLA strings or lithium / LiFePO4 cabinet, total runtime) is sized by ATENCO engineers according to UPS capacity, load level, battery chemistry and backup-time target. Lithium battery support requires compatible cabinet design, BMS communication and project-specific charging / runtime settings.

ComponentSpecification
UPS Cabinet DimensionsBy cabinet configuration; common cabinet sizes include 600 × 850 × 1200 mm, 600 × 850 × 2000 mm and 1200 × 850 × 2000 mm
UPS Cabinet WeightBy model / cabinet configuration
Power Module (W × D × H)440 × 620 × 130 mm
Power Module Weight40 kVA = 33 kg; 50 kVA = 34 kg; 60 kVA = 35 kg
Form FactorModular cabinet; external battery system by configuration
Protection ClassIP20
ColourBlack

Noise Levels

ConfigurationNoise (dB at 1 m)
Smaller cabinet configurations<66 dB
Larger cabinet configurations<73 dB

Cable sizing, external breaker ratings and protection coordination must follow local electrical code, installation method, cable type, ambient temperature, grouping, voltage drop, upstream / downstream protection and project electrical design.

InterfaceDetails
Display7″ TFT touchscreen standard / 10″ optional with mimic diagram and event history
RS-232Serial port for local monitoring software
RS-485For Modbus RTU communication and BMS / SCADA integration by configuration
Parallel PortFor N+X parallel operation up to 6 units
LBS PortLoad Bus Synchronization for dual-bus / synchronized multi-system designs
BMS PortBattery Management System interface
Dry Contact PortConfigurable contact port for status signalling
EPO & REPOStandard – Emergency Power Off / Remote Emergency Power Off
BAT_T PortOptional battery temperature sensor connection
Intelligent Slot Cards (Optional)TM550 SNMP card (network monitoring, web access, NMS / BMS integration); relay card (dry-contact integration)
FW / SW UpgradeOnline upgrade in bypass mode
SoftwareLocal monitoring software via RS-232 / RS-485; SNMP management software via TM550 card

Inverter Mode Overload

Load LevelDurationAction
105–110%60 minutesOverload protection / sustained within limit
110–125%10 minutesOverload protection
125–150%1 minuteOverload protection
>150%1.2 secondsShut down inverter

Bypass Mode Overload

Load LevelDurationAction
30 °C: ≤135%Long termSustained on bypass
40 °C: ≤125%Long termSustained on bypass
>1000%100 msProtection trip

System Protection & Alarm

FunctionBehaviour
Overheat (Line Mode)Switch to Bypass
Overheat (Battery Mode)Shut down UPS immediately
Self-DiagnosticsUpon Power-On and Software Control
LCD AlarmsLine Voltage, Bypass Mode, Battery Low, Battery Fault, Overload, UPS Fault
Audible AlarmsLine Failure, Battery Low, Overload, System Fault
EPO ActionShut down UPS immediately
ParameterSpecification
Operating Temperature0°C to 40°C
Storage Temperature−25°C to 55°C
Humidity0–95% RH non-condensing
Altitude<1000 m without derating; derating required above 1000 m
ClearanceMinimum front and rear clearance per installation manual for ventilation and maintenance
Safety StandardsIEC/EN 62040-1, IEC/EN 62477-1
EMC StandardsIEC/EN 62040-2 (IEC 61000-2-2, IEC 61000-4-2/-3/-4/-5/-6/-8/-11)
Performance StandardsIEC 62040-3:2021, EN IEC 62040-3:2021
CoolingForced air (fan); modular module cooling
InstallationIndoor use only
ApplicationsMedium-to-large data centers, core IT rooms, telecom switching centers, industrial automation rooms, utility / transport infrastructure, healthcare facility IT and government infrastructure requiring 40–600 kVA modular UPS with VRLA or lithium battery systems.

Incompatible loads: This series of products is not compatible with energy-feedback loads, including but not limited to CT machines in the medical field, cutting machines in the semiconductor industry, and all types of elevators or other motor-driven equipment that incorporate energy-feedback inverters at the front end – unless reviewed and approved by ATENCO engineering.

Downloads

TM66E Modular 40–600 kVA Datasheet – Coming soon EN
TM66E Modular 40–600 kVA User Manual – Coming soon EN
TM550 SNMP Card Manual EN

Ideal For

TM66E Modular 40–600 kVA is designed for medium-to-large three-phase critical-power systems requiring modular scalability, PF 1.0 output, VRLA or lithium battery flexibility, 360–600 Vdc battery bus and N+X parallel redundancy up to 6 units. It is best suited for data-center power rooms, telecom core sites, industrial automation rooms, utility and transportation infrastructure, public-sector critical IT and security command facilities where high-capacity modular UPS protection is required.

Data-center power rooms, server halls and co-location facilities backed up by ATENCO TM66E Modular 40-600 kVA modular three-phase UPS

Data Center Power Rooms & Server Halls

Medium-to-large modular three-phase UPS protection for data-center power rooms, server halls, storage clusters, core switching rooms and co-location facilities requiring PF 1.0 output, 40 / 50 / 60 kVA hot-swappable modules, VRLA or lithium battery systems and N+X redundancy.

Telecom core sites, switching centers and backbone network nodes backed up by ATENCO TM66E Modular 40-600 kVA modular three-phase UPS

Telecom Core & Switching Sites

Modular UPS backup for telecom core sites, switching centers, transmission rooms, MSC / aggregation facilities and backbone network nodes requiring scalable three-phase power, external battery autonomy, Power Walk-In generator compatibility and LBS-ready redundancy.

PLC, SCADA and DCS rooms with industrial automation infrastructure backed up by ATENCO TM66E Modular 40-600 kVA modular three-phase UPS

Industrial Automation & Process Control

Online modular UPS protection for PLC / SCADA servers, DCS rooms, industrial control servers, instrumentation panels and process-control infrastructure supplied from plant three-phase distribution – excluding regenerative or energy-feedback loads unless approved by ATENCO engineering.

Utility control rooms, substation communication systems and energy infrastructure backed up by ATENCO TM66E Modular 40-600 kVA modular three-phase UPS

Utility, Energy & Substation Control Rooms

Three-phase modular UPS for utility control rooms, substation communication systems, energy infrastructure, grid-monitoring rooms and electrical control centers requiring centralized backup power, external battery system design and high-capacity modular redundancy.

Airport technical rooms, railway and metro control centers and transport infrastructure IT backed up by ATENCO TM66E Modular 40-600 kVA modular three-phase UPS

Transportation & Infrastructure Control Centers

UPS protection for airport technical rooms, railway and metro control centers, traffic management rooms, tunnel communication systems and transport infrastructure IT requiring scalable 40–600 kVA modular backup and generator-compatible operation.

Government data rooms, public-safety command centers and security operations centers backed up by ATENCO TM66E Modular 40-600 kVA modular three-phase UPS

Government, Security & Public-Sector Critical IT

Modular three-phase UPS for government data rooms, public-safety command centers, security operations centers, emergency communication rooms and public-sector critical IT where PF 1.0 output, SNMP / BMS integration and N+X redundancy are required.

TM66E Modular 40–600 kVA UPS FAQ

Answers about TM66E Modular 40–600 kVA modular three-phase UPS architecture, VRLA / lithium battery support, PF 1.0 output, 40 / 50 / 60 kVA hot-swappable power modules, N+X parallel operation and Load Bus Synchronization.

What is the TM66E Modular 40–600 kVA UPS?
TM66E Modular 40–600 kVA is a transformerless modular three-phase online double-conversion UPS platform with VRLA and lithium battery support. It uses 40 / 50 / 60 kVA hot-swappable power modules, 3-level IGBT topology and hot-swappable power, bypass, monitoring and ECU control modules. Output PF is 1.0 (kW = kVA), AC-mode efficiency reaches up to 96%, and the battery system uses external VRLA lead-acid or lithium (LiFePO4) batteries with a 360–600 Vdc bus and charging current up to 20 A by configuration. Common cabinet configurations include 80, 120, 200, 300, 320, 400, 500 and 600 kVA; final capacity and redundancy are configured by module quantity and project design.
What is the difference between TM66E Modular 40–600 kVA and TM66E Modular 10–150 kVA?
TM66E Modular 40–600 kVA uses larger 40 / 50 / 60 kVA hot-swappable power modules, supports VRLA or lithium (LiFePO4) battery systems, uses a 360–600 Vdc battery bus, and reaches up to 96% AC-mode efficiency. TM66E Modular 10–150 kVA uses smaller 10 / 15 / 20 / 25 / 30 kVA hot-swappable power modules, external VRLA-only battery systems, programmable ±180 to ±300 Vdc battery bus, and up to 95.8% AC-mode efficiency. Choose 10–150 kVA for smaller rack-cabinet projects with VRLA external batteries; choose 40–600 kVA for medium-to-large modular UPS projects requiring lithium support, larger power modules, higher capacity and higher efficiency.
Can the TM66E Modular 40–600 kVA be paralleled for redundancy?
Yes. TM66E Modular 40–600 kVA supports direct parallel operation for capacity expansion or N+X redundancy up to 6 units, subject to project design. Shared-battery parallel configuration is supported by configuration. A Load Bus Synchronization (LBS) port is available for dual-bus or coordinated multi-system designs. The parallel kit, including cables and configuration, is specified at order.
What battery options does the TM66E Modular 40–600 kVA support?
TM66E Modular 40–600 kVA supports external VRLA lead-acid maintenance-free or lithium (LiFePO4) battery systems by project configuration, with a 360–600 Vdc battery bus and charging current up to 20 A by model and configuration. Lithium battery cabinets require compatible cabinet design, BMS communication and project-specific charging and runtime settings. ATENCO engineers size the battery configuration according to UPS capacity, load level, target backup time, battery chemistry and site requirements.
Can the TM66E Modular 40–600 kVA run on a generator?
Yes. TM66E Modular 40–600 kVA supports a wide 138–485 Vac input window with Power Walk-In to reduce start-current impact on generator capacity when the generator is properly sized and configured. The UPS operates at 100% load from 305–485 Vac and derates to 40% load below 305 Vac. Input PF ≥0.99 and input THDi ≤3% help reduce upstream electrical stress.
What monitoring options does the TM66E Modular 40–600 kVA support?
TM66E Modular 40–600 kVA provides a 7-inch TFT touchscreen HMI standard, with 10-inch optional by configuration, plus mimic diagram, history logs and fault logs. Communications include RS-232, RS-485, parallel, LBS, BMS and dry-contact ports. Optional intelligent-slot cards include the TM550 SNMP card for network monitoring, web access, event alerts and NMS / BMS integration, plus relay-card options for dry-contact integration. Modbus RTU via RS-485 supports BMS / SCADA integration by configuration. Battery temperature sensor is optional. FW / SW online upgrade is supported in bypass mode.
What is LBS synchronization on the TM66E Modular 40–600 kVA?
LBS, or Load Bus Synchronization, is available on TM66E Modular 40–600 kVA for dual-bus or synchronized multi-system designs. It coordinates output synchronization between independent UPS systems in applications such as dual power paths or STS-supported architectures. Availability and configuration depend on project design.
Does TM66E Modular 40–600 kVA support lithium batteries?
Yes. TM66E Modular 40–600 kVA supports external VRLA lead-acid or lithium (LiFePO4) battery systems with a 360–600 Vdc battery bus by project configuration. Lithium systems require compatible cabinet design, BMS communication and project-specific charging and runtime settings confirmed during sizing. For larger capacities, use TM66E Large Modular 400–1200 kVA.
Is TM66E Modular 40–600 kVA hot-swappable?
Yes. TM66E Modular 40–600 kVA is a modular platform with hot-swappable power modules, bypass module, monitoring module and ECU control module. Power modules can be added, removed or replaced within cabinet capacity, supporting capacity expansion and reduced-downtime maintenance by approved procedure. Battery systems are external VRLA or lithium cabinets by project configuration, not built-in hot-swappable battery modules.
Which applications is the TM66E Modular 40–600 kVA not recommended for?
TM66E Modular 40–600 kVA, like the TM66E series, is not compatible with regenerative / energy-feedback loads, including CT machines, semiconductor cutting machines, elevators and motor-driven equipment with front-end feedback inverters, unless reviewed and approved by ATENCO engineering. It is also not the right choice when the protected load requires single-phase output; use TM11E, RM11E, TM31E or RM31E instead according to input / output architecture and capacity. For smaller modular UPS projects, use TM66E Compact 30–75 kVA or TM66E Modular 10–150 kVA. For capacities above 600 kVA, use TM66E Large Modular 400–1200 kVA. For transformer-based galvanic isolation, use TM33-ET.
What is the advantage of TM66E Modular 40–600 kVA over smaller modular UPS systems?
TM66E Modular 40–600 kVA provides higher scalable capacity, larger 40 / 50 / 60 kVA hot-swappable power modules, VRLA or lithium battery support, 360–600 Vdc battery bus, up to 96% AC efficiency and N+X parallel operation up to 6 units. It is better suited for medium-to-large data centers, telecom core sites, industrial control rooms and infrastructure projects requiring modular UPS expansion and battery-chemistry flexibility.
TM66E Modular 40–600 kVA Project Sizing

Size Your TM66E Modular 40–600 kVA UPS Project

Share your three-phase load list, target backup time, redundancy plan, site voltage, generator details, VRLA / lithium battery preference, BMS requirement and monitoring requirements. ATENCO will recommend the suitable TM66E Modular 40–600 kVA configuration with 40 / 50 / 60 kVA hot-swappable power modules, external VRLA or lithium battery system, parallel topology, Load Bus Synchronization (LBS), HECO mode and TM550 SNMP / relay-card options matched to your project.

1

Send Project Requirements

Share three-phase load in kW / kVA, target runtime, redundancy requirement, site nominal voltage, generator details, VRLA / lithium battery preference, BMS requirement and monitoring preferences such as TM550 SNMP, RS-485 / Modbus RTU, relay card, BMS or NMS integration.

2

Receive UPS Selection & Sizing

ATENCO engineers recommend the suitable TM66E Modular configuration: 40 / 50 / 60 kVA power-module configuration, common cabinet capacity, external VRLA or lithium battery system, 360–600 Vdc battery bus, parallel topology, LBS design and matching TM550 SNMP or relay-card accessories.

Load & Runtime Sizing
Parallel / N+X / LBS Design
VRLA / Lithium Battery Systems
Scroll to Top