Outdoor Online UPS System 1–10 kVA

PowTerra is a project-configured outdoor online UPS system for telecom, CCTV, traffic control, edge networks and remote infrastructure sites. It combines true online double-conversion protection, pure sine-wave output, integrated battery backup and an outdoor enclosure with protection up to IP55 by configuration and integrated thermal management (cooling and heating by project design).

Surge and transient protection, monitoring, battery capacity, autonomy and cabinet layout are selected according to the installation environment. Designed and tested in accordance with applicable CE, EMC, LVD and IEC 62040 requirements by configuration.

Online Double-Conversion Outdoor Cabinet Platform Integrated Thermal Management

Engineered for Reliable Outdoor Power

Project-configured outdoor UPS protection combining VFI power conversion, weather-resistant enclosure design, thermal management, battery backup and remote monitoring.

Online Double-Conversion Protection

Provides regulated pure sine-wave output and 0 ms transfer time between online and battery operation for telecom, CCTV, traffic systems, edge networks and other remote infrastructure loads.

Outdoor Cabinet Platform

Weather-resistant enclosure configurations are selected according to site exposure, required IP protection, internal equipment layout, cable-entry direction, ventilation and service-access requirements.

Integrated Thermal Management

Air conditioning, fan cooling, heat-exchanger and heating options can be configured according to ambient temperature, internal heat load, battery type and cabinet design.

Surge & Transient Protection Options

Surge-protection devices and outdoor power-distribution components can be integrated according to site exposure, grounding arrangement, lightning-protection design and project requirements.

Flexible Battery Runtime

Battery type, DC voltage, capacity and cabinet allocation are selected according to the connected load, required backup time, environmental conditions and available internal space.

Monitoring & Alarm Integration

SNMP, Modbus, RS-232, USB and dry-contact options are available by configuration for remote supervision, alarm reporting and integration with building-management or control-room systems.

Configure Your PowTerra System

Optional monitoring, signalling, battery and enclosure features are selected according to the UPS rating, site environment, runtime target and project requirements.

ATENCO PowTerra outdoor UPS cabinet configuration with battery compartment and thermal management

Cabinet Configuration Options

Cabinet size, IP protection level, battery compartment, cable-entry arrangement, thermal-management system and service access are selected according to the installation environment and project design.

ATENCO VRLA battery system for PowTerra outdoor UPS runtime

Battery Runtime Options

AGM / VRLA battery systems are sized according to connected load, required backup time, ambient conditions and available cabinet space. LFP battery solutions may be evaluated for approved configurations requiring lower weight, longer cycle life or extended service life.

ATENCO SNMP monitoring card for PowTerra outdoor UPS

SNMP & Remote Monitoring

Optional network monitoring provides UPS status, alarms, event history and remote supervision. Supported protocols and card type vary according to the installed UPS model and communication configuration.

ATENCO relay and dry-contact card for PowTerra outdoor UPS alarm and signalling integration

Relay & Dry-Contact Interface

Optional dry-contact interfaces provide configurable alarm outputs and signal inputs for utility failure, UPS status, battery alarms and integration with building-management or external monitoring systems. Available contacts and functions vary by model and configuration.

Reference Technical Configurations

The values below represent common PowTerra reference configurations. Final capacity, phase, PF, IP rating, cabinet size, battery capacity, thermal-management package and communication options are confirmed according to project requirements and approved design.

1–3 kVA Models

Specification1 kVA2 kVA3 kVA
Full NamePowTerra Outdoor Online UPS
TopologyOnline Double-Conversion (VFI), DSP Controlled
Phase1P–1P (Single Phase In / Single Phase Out)
Form FactorIP55 Outdoor Cabinet (galvanized steel, powder-coated)
Capacity1000 VA / 800W2000 VA / 1600W3000 VA / 2400W
Output Power Factor0.8
Battery12V VRLA (sealed lead-acid), internal
Cabinet FeaturesIntegrated 600W A/C, lightning SPD, anti-theft lock
Operating ModesNOR (Online), ECO, Bypass, Battery
DisplayLCD panel with status indicators
StandardsIEC 62040-1, IEC 62040-2, IEC 62040-3

6–10 kVA Models

Specification6 kVA10 kVA
Full NamePowTerra Outdoor Online UPS
TopologyOnline Double-Conversion (VFI), 3-Level IGBT, DSP
Phase1P–1P (Single Phase In / Single Phase Out)
Form FactorIP55 Outdoor Cabinet (galvanized steel, powder-coated)
Capacity6000 VA / 5400W10000 VA / 9000W
Output Power Factor0.9
Battery12V VRLA (16–20 blocks configurable)
DisplayLCD panel; optional SNMP remote monitoring
Operating ModesNOR (Online), ECO, GEN, Bypass, Battery
Cabinet FeaturesIntegrated 600W A/C, lightning SPD, ventilation, anti-theft lock
Intelligent Slot1× slot (SNMP, Relay or Modbus card by configuration)
StandardsIEC 62040-1, IEC 62040-2, IEC 62040-3

1–3 kVA Models

Specification1 kVA2 kVA3 kVA
Input Voltage Range100–300Vac (wide range for unstable grid & generators)
Input PF≥0.98 at 100% load
Input Frequency40–70Hz auto-sensing
Output Voltage220/230/240Vac selectable, ±2% regulation
Output PF0.8
Output WaveformPure sinewave
Output Frequency (line)46–54Hz or 56–64Hz (synced to mains)
Output Frequency (battery)50/60Hz ±0.5Hz
THDv≤3% linear / ≤5% non-linear
Transfer Time0ms (AC→Battery); 4ms (Inverter→Bypass)
Crest Factor3:1
Efficiency (Online)88%90%90%
Efficiency (ECO)95%96%96%

6–10 kVA Models

Specification6 kVA10 kVA
Input Voltage Range100–300Vac (176–300V at 100%; 100–176V derated)
Input PF≥0.99
Input THDi≤5%
Input Frequency40–70Hz auto-sensing
Output Voltage208/220/230/240Vac selectable, ±1% regulation
Output PF0.9
Output WaveformPure sinewave
THDv≤2% linear / ≤5% non-linear
Transfer Time0ms (AC→Battery); 4ms (Inverter→Bypass)
Crest Factor3:1
Efficiency (Online)Up to 90%Up to 90%
Efficiency (ECO)Up to 96%Up to 97%

1–3 kVA – Internal VRLA Batteries

Specification1 kVA2 kVA3 kVA
Battery Type12V VRLA (Sealed Lead-Acid)
Battery Configuration2×12V (24Vdc)4×12V (48Vdc)6×12V (72Vdc)
Battery Capacity100Ah (internal, large capacity for extended runtime)
Backup Time (full load)>2 hours>2 hours>2 hours
Max Charge Current5A5A10A
Recharge Time8–10 hours to full
Battery Life3–5 years at 25°C (extended with A/C temperature control)
Deep Discharge ProtectionAuto shutdown at low voltage threshold

6–10 kVA – External VRLA Battery Blocks

Specification6 kVA10 kVA
Battery Type12V VRLA (Sealed Lead-Acid)
Bus Voltage192 / 216 / 240Vdc (16/18/20 × 12V blocks)
Recommended Capacity7–9Ah per block (configurable for runtime needs)
Max Charge Current6A (adjustable up to 12A)6A (adjustable up to 12A)
Recharge to 90%4 hours
Battery Life3–5 years at 25°C (extended with A/C)
Battery LocationInternal battery compartment within outdoor cabinet

1–3 kVA Outdoor Cabinets

Specification1 kVA2 kVA3 kVA
Form FactorIP55 Outdoor Cabinet (floor-standing)
Cabinet MaterialGalvanized steel, powder-coated (RAL 7035 Light Grey)
Cabinet Dimensions (W×D×H)500×450×850mm600×500×1000mm600×600×1200mm
Weight (incl. batteries)≈80kg≈120kg≈160kg
DoorLockable front door with anti-theft lock
Cable EntryBottom entry with waterproof cable glands
Air Conditioning600W integrated A/C, thermostat-controlled
Noise<55dB at 1m (including A/C)
ColourRAL 7035 (Light Grey)

6–10 kVA Outdoor Cabinets

Specification6 kVA10 kVA
Form FactorIP55 Outdoor Cabinet (floor-standing)
Cabinet MaterialGalvanized steel, powder-coated (RAL 7035 Light Grey)
Cabinet Dimensions (W×D×H)800×600×1400mm800×800×1600mm
Weight (incl. batteries)≈200kg≈280kg
DoorLockable front door with anti-theft lock
Cable EntryBottom entry with waterproof cable glands
Air Conditioning600W integrated A/C, thermostat-controlled
HeaterAuto-heater below 0°C for battery protection
Noise<55dB at 1m<58dB at 1m
ColourRAL 7035 (Light Grey)

1–3 kVA Communication

InterfaceDetails
RS-232DB9 serial port for local monitoring
SNMP Slot1× intelligent slot (optional SNMP monitoring card)
Dry ContactRelay output for remote alarm (optional card)
Output TerminalHardwired terminal block output (L+N+G)
DisplayLCD panel on cabinet door with status indicators
OptionalSNMP monitoring card, Dry contact relay card

6–10 kVA Communication

InterfaceDetails
RS-232DB9 serial port
RS-485Built-in for Modbus RTU / multi-drop monitoring
Intelligent Slot1× slot (SNMP, Modbus or Relay card by configuration)
EPOEmergency Power Off connector
Dry ContactRelay outputs for remote alarm signalling
Output TerminalHardwired terminal block (L+N+G)
DisplayLCD panel on cabinet door
OptionalSNMP monitoring card, Modbus card, Relay card

1–3 kVA – Online Mode

Load LevelDurationAction
105–125%1 minuteTransfer to bypass
125–130%30 secondsTransfer to bypass
>130%0.2 secondsTransfer to bypass

1–3 kVA – Battery Mode

Load LevelDurationAction
105–125%1 minuteShutdown
125–130%10 secondsShutdown
>130%0.2 secondsImmediate shutdown

6–10 kVA – Online Mode

Load LevelDurationAction
≤110%60 minutesSustained
≤125%10 minutesTransfer to bypass
≤150%1 minuteTransfer to bypass
>150%0.5 secondsTransfer to bypass

6–10 kVA – Battery Mode

Load LevelDurationAction
≤110%10 minutesSustained
≤125%1 minuteShutdown
≤150%10 secondsShutdown
>150%0.5 secondsImmediate shutdown
ParameterSpecification
Operating Temperature (outdoor)−10°C to +55°C (with integrated A/C)
A/C Cooling Capacity600W, thermostat-controlled auto start/stop
Auto HeaterActivates below 0°C for battery protection
Storage Temperature−25°C to +70°C
Humidity0–95% RH non-condensing
Altitude (Full Load)<1500m – derate above: 2000m=90%, 2500m=85%, 3000m=80%
Max Operating Altitude3000m (suitable for mountain installations)
Protection ClassIP55 (dust-tight, protected against water jets)
Lightning ProtectionIntegrated SPD (Surge Protection Device)
SafetyIEC 62040-1, IEC 62040-2, IEC 62040-3
EMCIEC/EN 62040-2
CabinetGalvanized steel, anti-corrosion, anti-UV coating
Cooling (internal)Forced air fans + A/C closed-loop cooling

Recommended Circuit Breakers (external)

Breaker6 kVA10 kVA
Input (1P)40A63A
Output (1P)40A63A
Battery (2P DC)50A63A

Downloads

PowTerra 1-3 kVA Datasheet EN
PowTerra 6-10 kVA Datasheet – Coming soon
PowTerra 1-10 kVA User Manual EN

Ideal for Outdoor Infrastructure

Designed for projects where power quality, temperature control, dust, moisture, remote access and backup time must be engineered as one integrated system.

Outdoor UPS for traffic signal and ITS systems

Traffic Signals & ITS

Outdoor UPS protection for traffic controllers, roadside ITS cabinets, intersection cameras and transport-monitoring equipment exposed to unstable utility power, dust, moisture and temperature variation.

Climate controlled outdoor UPS cabinet for CCTV security and surveillance

CCTV & Security Systems

Climate-managed outdoor power protection for IP CCTV, NVRs, access control, perimeter monitoring and security-network equipment installed in exposed or remote locations.

Telecom outdoor UPS cabinet for 5G and edge network sites

Telecom & Edge Networks

Outdoor UPS systems for telecom shelters, access equipment, edge network cabinets, small cell sites and remote communications infrastructure requiring online power protection, battery backup and thermal management.

Outdoor UPS for remote industrial SCADA PLC panels

Remote Industrial Control

Stable online power for SCADA equipment, PLC panels, monitoring instruments and automation-control cabinets at remote industrial sites, subject to load characteristics and environmental requirements.

Harsh climate outdoor UPS cabinet with thermal management

Harsh-Climate Installations

Configurable enclosure and thermal-management options for hot, cold, dusty or high-humidity environments where internal temperature and equipment protection must be controlled.

Remote site UPS backup for mountain repeater stations and isolated infrastructure

Rural, Mountain & Isolated Sites

Backup power for repeater stations, weather-monitoring systems, remote communications and infrastructure sites with limited maintenance access.

Not sure which outdoor UPS configuration fits your site? Share your load list, backup-time target, site voltage, ambient temperature and cabinet location – ATENCO will size the PowTerra cabinet, battery system and monitoring options.

Project Configuration

Configured Around Your Outdoor Site

PowTerra is configured according to the connected load, backup-time target, site voltage, input/output phase, installation location, ambient temperature range, required IP protection, battery system and monitoring requirements.

Connected load and peak power
Required backup time
Site voltage and input/output phase
Ambient temperature range
Cabinet location and outdoor exposure
Battery type, capacity and runtime requirement
Remote monitoring and dry-contact requirements
Surge-protection and grounding requirements

Share these site details with ATENCO and we will recommend the suitable PowTerra capacity, cabinet layout, battery system, thermal-management package and communication options.

PowTerra Outdoor UPS FAQ

Common questions about project configuration, IP rating, thermal management, monitoring and applications.

What is an outdoor UPS cabinet?

An outdoor UPS cabinet combines online UPS power protection, battery backup, enclosure protection, thermal management and monitoring options for equipment installed in outdoor or semi-outdoor locations. PowTerra is configured according to the site voltage, load, required runtime, ambient temperature, IP protection level, installation location and communication requirements.

Is PowTerra a fixed model or customized outdoor UPS system?

PowTerra is a project-configured outdoor UPS platform rather than one fixed cabinet model. UPS capacity, cabinet size, IP protection, battery system, runtime, cooling or heating method, communication options and input/output phase are selected according to the approved project design.

Is PowTerra IP55 or IP56?

PowTerra cabinet protection is selected according to the approved project configuration. IP55 or IP56 enclosure options may be available depending on cabinet design, thermal-management method, cable entry and site conditions. The final IP rating must be confirmed in the project proposal.

Can PowTerra support telecom and CCTV equipment?

Yes. PowTerra is designed for telecom shelters, small cell sites, edge network cabinets, IP CCTV systems, NVRs, traffic controllers, perimeter security and other remote infrastructure requiring stable online power, battery backup and environmental protection.

Does PowTerra include air conditioning?

PowTerra can be configured with air conditioning, fan cooling, a heat exchanger, heating or a combination of thermal-management methods, depending on ambient temperature, internal heat load, battery type and cabinet design. The thermal-management package is selected as part of the approved project configuration.

What backup time can PowTerra provide?

Backup time depends on the connected load, battery capacity, battery type, ambient temperature, allowable cabinet space and required autonomy. ATENCO can prepare a project-specific runtime calculation based on the load list and target backup time.

Can PowTerra be monitored remotely?

Yes. Depending on the installed UPS and communication configuration, PowTerra may support SNMP, Modbus, RS-232, USB and dry-contact alarm interfaces for integration with network-management, building-management and control-room systems.

Can surge-protection devices be integrated?

Yes. Surge-protection devices and coordinated power-distribution protection may be integrated according to site exposure, grounding design and the approved project scope. Protection against direct lightning effects requires a complete site lightning-protection and earthing design and should not be assumed from the UPS cabinet alone.

Which industries use PowTerra outdoor UPS cabinets?

PowTerra is used for telecom and edge networks, CCTV and security systems, traffic and ITS infrastructure, remote SCADA and industrial-control sites, weather-monitoring systems, repeater stations and rural or isolated infrastructure where power quality, temperature, dust, moisture and remote access must be considered together.

Related indoor UPS series: TM11E indoor tower, RM11E rack/tower, single-phase UPS overview.

PowTerra Outdoor UPS Platform

Configure the Right Outdoor UPS System
for Your Site

Send us your connected load, required backup time, site voltage, installation location, ambient temperature range, available cabinet space and monitoring requirements. ATENCO will recommend the suitable PowTerra capacity, battery system, cabinet configuration, thermal-management design and communication options for your project.

Site-Based Configuration
Battery Runtime Calculation
Outdoor Cabinet Engineering